Salisbury Electrical Protection Page 9

For more information, call Western Safety Products at 206-264-0808 or email sales@westernsafety.com.

Credit Card Images

Grounding Sets
  24309 Typical ground cluster set
Single Grounding Jumpers require the least amount of equipment. Sets of single jumpers represent simplicity and versatility for personal protective grounding applications. Suggestions for consideration include: 2653 Drawstring Bag for transporting and protection, 9998 pole mount bar with chain binder, 2103 screw ground rod and 60 ft. jumper for phase to ground rod connection.

Grounding Sets — Single Grounding Jumpers
Cat.
No.
Description ASTM
Grade
Weight
lbs. (kg)
Single Grounding Jumpers
24309 2 ea. #1895A Smooth Aluminum “C” Clamp 1.5”
1 pr. #2024A Ferrules
6 ft. #2138 2/0 Cu. Cable yellow
2 5.9 (2.7)
2299 2 ea. #1895A Smooth Aluminum "C" Clamp 1.5"
1 ea. #1928A Hanger Stud, 1 pr. #2027A Ferrules
6 ft. #2137 1/0 Cu. Cable
2 5.9 (2.7)
2309 2 ea. #1893A Serrated Aluminum “C” Clamp 1.5”
1 ea. #1928A Hanger Stud, 1 pr. #2027A Ferrules
6 ft. #2137 1/0 Cu. Cable
2 6.1 (2.8)
2319 2 ea. #1923A Smooth Aluminum “C” Clamp 2.4”
1 ea. #1928A Hanger Stud, 1 pr. #2620A Ferrules
10 ft. #2138 2/0 Cu. Cable
3 8.7 (3.9)
2320 1 ea. #1923A Smooth Aluminum “C” Clamp
1 ea. #4345 Aluminum Flat Jaw “T” Handle Clamp
1 pr. #2620A Ferrules, 15 ft. #2138 2/0 Cu. Cable
3 7.4 (3.4)
2321 2 ea. #1793A Bronze Duck Bill 556 KCM
1 ea. #2093A Hanger Stud, 1 pr. #2023A Ferrules
6 ft. #2137 1/0 Cu. Cable
2 5.4 (2.5)
2329 2 ea. #1921A Serrated Aluminum “C” Clamp 2.4”
1 ea. #1928A Hanger Stud, 1 pr. #2620A Ferrules
10 ft. #2138 2/0 Cu. Cable
3 9 (4.1)
2509 2 ea. #2514A Serrated Aluminum “C” Clamp 1.25”
1 ea. #1928A Hanger Stud, 1 pr. #2027A Ferrules
6 ft. #2137 1/0 Cu. Cable
2 6.1 (2.8)
2556 2 ea. #1852A Smooth Aluminum Duck Bill Clamp 1.66”
1 ea. #1858A Hanger Stud, 1 pr. #2027A Ferrules
6 ft. #2137 1/0 Cu. Cable
2 5.2 (2.4)
2558 2 ea. #1853A Serrated Aluminum Duck Bill Clamp 1.25”
1 ea. #1858A Hanger Stud, 1 pr. #2027A Ferrules
6 ft. #2137 1/0 Cu. Cable
2 5.5 (2.5)
2876 2 ea. #2531A Smooth Aluminum “C” Clamp 1.0”
1 ea. #2537A Hanger Stud, 1 pr. #2027A Ferrules
6 ft. #2137 1/0 Cu. Cable
2 4.9 (2.2)
9975 2 ea. #9985A Smooth Bronze “C” Clamp 1.0”
1 ea. #9983A Hanger Stud, 1 pr. #2023A Ferrules
6 ft. #2137 1/0 Cu. Cable
2 6.9 (3.1)
9982 2 ea. #9984A Smooth Bronze “C” Clamp 1.25”
1 ea. #9983A Hanger Stud, 1 pr. #2023A Ferrules
6 ft. #2137 1/0 Cu. Cable
2 8.3 (3.7)
Single Jumper Ground Sets
2881 6 ea. #2531A Smooth Aluminum “C” Clamps 795 KCM
3 ea. #2537A Hanger Studs, 3 pr. #2027A Ferrules
26 ft. #2137 1/0 Cu. Cable
2 22.4 (10.2)
2882 6 ea. #1893A Serrated Aluminum “C” Clamps 1.5”
3 ea. #1928A Hanger Studs, 3 pr. #2027A Ferrules
26 ft. #2137 1/0 Cu. Cable
2 22.8 (10.2)

Grounding Sets — Single Point Distribution Grounding Set
This Single Point Distribution Grounding Set creates an equal potential zone on the working structure. This is accomplished by bonding all conductors and the structure to a ground source using individual jumpers as shown in the adjacent drawing. Going from either the ground rod or the system ground to the pole mounted contact bar under the worker’s feet, to the jumpers bonding the conductors creates an equal potential zone allowing the lineman to work safely.
Cat.
No.
Description ASTM
Grade
Weight
lbs. (kg)
4246 Complete Distribution Grounding Set
10 ea. #2531A Smooth Aluminum “C” Clamps 795 KCM
1 ea. #9998 Aluminum Pole Mount Contact Bar
5 pr. #2026A Ferrules
3 ea. #2537A Hanger studs
60 ft. #2636 # Cu. Cable
1 ea. #2103 Screw Ground Rod w/ Connector
1 45.5 (20.6)

Grounding Sets — 3 Wire Universal Grounding Clusters & Sets
2534 1957 2547 1790
2685
Grounding Clusters are used to make it easy for a single line worker to apply multiple grounding jumpers on a three phase system. All clusters have an option of a ground lead by using the extra connection point on each cluster. Three wire clusters are recommended for three phase Delta systems. Complete grounding cluster assemblies are available from the factory. Specify cable size and length required and assembly will be made to your specifications.

Grounding Sets — 3 Wire Universal Grounding Clusters & Sets
Cat.
No.
Description ASTM
Grade
Weight
lbs. (kg)
2534 Cluster w/ 3 #2531 Smooth Jaw
1” Aluminum “C” Clamps
5 4.9 ( 2.2 )
2516 Cluster w/ 3 #1893 Serrated Jaw
1.5” Aluminum “C” Clamps
5 7.1 ( 3.2 )
1957 Cluster w/ 3 #1895 Smooth Jaw
1.5” Aluminum “C” Clamps
5 6.4 ( 2.9 )
1790 Cluster w/ 3 #1793 Smooth Jaw
556 KCM Bronze Duck Bill Clamps
4 6 ( 2.7 )
2547 Cluster w/ 3 #1852 Smooth Jaw
1.66” Aluminum Duck Bill Clamps
5 5.4 ( 2.5 )
2685 Assembled Ground Cluster Set
1 ea. #2516A Serrated Aluminum “C” Clamp 1.25” Cluster
74 ft. #2637 1/0 Cu. Cable
3 pr. #2027A Ferrules, 1 ea. #2103 Screw Ground Rod
1 ea. #2654 Storage Bag
2 54.2 ( 24.6 )
4248 Assembled Ground Cluster Set
1 ea. #1790 Smooth Bronze Duck Bill Cluster
76 ft. #2636 #2 Cu. Cable
3 pr. #2022A Ferrules, 1 ea. #2103 Screw Ground Rod
1 ea. #2654 Storage Bag
1 54.2 ( 24.6 )
Clusters are also available with Mounted Clamps.

Grounding Sets — 4 Wire Universal Grounding Clusters & Sets
2536 1794 2192
4247 Assembled Ground Set
Grounding Clusters are used to make it easy to apply multiple grounding jumpers easy for a single line worker. All clusters have an option of a ground lead by using the extra connection point on each cluster. Four wire clusters are recommended for three phase Wye systems. Complete grounding cluster assemblies are available from the factory. Specify cable size and length required and assembly will be made to your specifications.

Grounding Sets — 4 Wire Universal Grounding Clusters & Sets
Cat.
No.
Description ASTM
Grade
Weight
lbs. (kg)
2536 Cluster w/ 6 #2531 Smooth Jaw
1” Aluminum “C” Clamps
5 8.8 ( 4 )
2614 Cluster w/ 6 #1893 Serrated Jaw
1.5” Aluminum “C” Clamps
5 11.8 ( 5.4 )
2192 Cluster w/ 6 #1895 Smooth Jaw
1.5” Aluminum “C” Clamps
5 11.8 ( 5.4 )
1794 Cluster w/ 6 #1793 Smooth Jaw
556 KCM Bronze Duck Bill Clamps
4 9 ( 4.1 )
2604 Cluster w/ 6 #1852 Smooth Jaw
1.66” Aluminum Duck Bill Clamps
5 6.2 ( 2.8 )
2682 Assembled Ground Cluster
1 ea. #1794A Smooth Bronze Duck Bill Cluster
18 ft. #2636 #2 Cu. Cable
3 pr. #2022A Ferrules
1 ea. #2654 Storage Bag
1 14.5 ( 6.6 )
4247 Assembled Ground Cluster
1 ea. #2536 Smooth Aluminum “C” Cluster
18 ft. #2637 1/0 Cu. Cable
3 pr. #2027A Ferrules
1 ea. #2654 Storage Bag
2 18 ( 8.2 )
Clusters are also available with Mounted Clamps.

Grounding Sets — 4 Way Connector
2680 2374 4 Way Connector

Grounding Sets — 4 Way Connector
Cat.
No.
Description ASTM
Grade
Weight
lbs. (kg)
2680 Four Way Connector Ground Set
21 kA 15 cycles
1 #2374A Four Way Connector w/ Sleeves
4 #1895A 1.5” Smooth Jaw Clamps w/ Sleeves
1 #2427A Double Hanger Stud, 1 #2402A Contact Stud
34 ft. #2137 1/0 Cu. Cable
4 pr. #2027 Ferrules
5 28 ( 12.7 )
2374 Four Way Connector Only 1.8 (.8)

Grounding Sets — For Special Applications
2684 4276
Listed are some typical complete personal protection ground sets for common line construction. These sets, although practical for many applications, are shown as a guide to help determine individual system needs and for ease of ordering. Variations of these sets may be requested to meet specific situations or user preferences. Your local Salisbury representative can answer any questions you have on personal protection grounding needs and applications.

Grounding Sets — For Special Applications
Cat.
No.
Description ASTM
Grade
Weight
lbs. (kg)
Complete 3 Phase Delta
4249 2 ea. #20880A Cluster Bar
7 ea. #2531A Smooth Aluminum “C” Clamp 795 KCM
86 ft. #2637 1/0 Cu. Cable, 4 pr. #2027A Ferrules
2 ea. #2537A Hanger Studs, 1 ea. #2654 Storage Bag
1 ea. #2103 Screw Ground Rod
2 63.5 ( 28.8 )
2684 2 ea. #20880A Cluster Bar
7 ea. #1893A Serrated Aluminum “C” Clamp 1.5”
84 ft. #2637 1/0 Cu. Cable, 4 pr. #2027A Ferrules
2 ea. #1928A Hanger Studs, 1 ea. #2654 Storage Bag
1 ea. #2103 Screw Ground Rod
2 63.5 ( 28.8 )
Complete 4 Wire Wye
4276 1 ea. #20880A Cluster Bar
7 ea. #2531A Smooth Aluminum “C” Clamp 795 KCM
32 ft. #2637 1/0 Cu. Cable, 4 pr. #2027A Ferrules
3 ea. #2537A Hanger Studs, 1 ea. #2654 Storage Bag
2 34 ( 15.4 )

Grounding Sets — Dead Front Grounding Jumpers & Elbows
Elbow Grounding Set
Dead Front Ground Sets are supplied with an insulated grounding elbow, yellow jacketed copper grounding cable, and a 1815 bronze flat jaw ground clamp for the ground connection. Grounding Elbows are equipped with arc quenching tips as provided on standard load break elbows.
Both 15kV and 25kV elbows are available with connectors for 1/0 or 2/0 cable. Assembled sets for 15kV and 25kV are available for single phase or three phase grounding requirements. Standard three phase sets have a 4 ft. tail connecting to a 2374 four wire connector with 2 ft. leads for the elbows. Sets can be factory assembled to customer specifications.

Grounding Sets — Dead Front Grounding Jumpers & Elbows
Cat.
No.
Description Weight
lbs. (kg)
Insulating Grounding Elbows
2910 15kV Elbow w/ 1/0 Cable Connector 1.7 ( .7 )
2912 15kV Elbow w/ 2/0 Cable Connector 1.7 ( .7 )
2935 25kV Elbow w/ 1/0 Cable Connector 2 ( .9 )
2936 25kV Elbow w/ 2/0 Cable Connector 2 ( .9 )
Assembled Grounding Sets
2961 15kV Single Phase, 6 ft. 1/0 Cable w/ Bag 10 ( 4.5 )
2962 15kV Single Phase, 6 ft. 1/0 Cable w/o Bag 8 ( 3.6 )
2963 15kV Three Phase, 1/0 Cable w/ Bag 22 ( 10 )
2971 25kV Single Phase, 6 ft. 1/0 Cable w/ Bag 13 ( 5.9 )
2973 25kV Three Phase, 1/0 Cable w/ Bag 24 ( 10.9 )

Grounding Cables
The yellow thermoplastic elastomer jacketed cable is the standard for grounding service. It provides a combination of economy, flexibility, and durability. The service temperature ranges from 200º to -50ºF. ASTM F 855 Type I. The black thermoplastic elastomer jacketed cable has a smaller diameter and thinner jacket material giving it better flexibility than the yellow cable. The service temperature ranges from 200º to -50ºF. ASTM F 855 Type I The transparent flexible thermoplastic (PVC) jacketed cable allows easy inspection for strand breakage. The flexibility decreases with low temperatures. The minimum recommended service temperature is 0ºF. ASTM F Type III.
Grounding Cables are made with extra flexible strand of soft drawn #30 AWG (.01”) copper and are available in three different jackets.

Grounding Cables
Cat.
No.
Size Strand
Dia.
in. (mm)
Jacket
in. (mm)
Short Circuit
AMPS, RMS, 60 Hz
Continuous
Current
AMPS, RMS, 60 Hz
Weight / 1000 ft
lbs. (kg)
  15 Cycles 30 Cycles  
Yellow
2136 #2-665W .35 (8.9) .5 (12.7) 14500 10000 200 282 (127)
2137 1/0-1064W .45 (11.4) .62 (15.7) 21000 15000 250 488 (221)
2138 2/0-1330W .49 (12.4) .65 (16.5) 27000 20000 300 537 (243)
2139 4/0-2109W .62 (17) .83 (21.1) 43000 30000 400 836 (379)
Black
2636 #2-665W .35 (8.9) .47 (12) 14500 10000 200 263 (119)
2637 1/0-1064W .45 (11.4) .58 (14.7) 21000 15000 250 404 (183)
2638 2/0-1330W .49 (12.4) .63 (16) 27000 20000 300 497 (225)
2649 3/0-1672W .55 (14) .72 (18.3) 36000 25000 350 680 (308)
2639 4/0-2109W .62 (17) .78 (19.8) 43000 30000 400 770 (349)
Clear
2128 #2-665W .35 (8.9) .53 (13.5) 14500 10000 200 289 (131)
2129 1/0-1064W .45 (11.4) .64 (16.3) 21000 15000 250 520 (235)
2133 2/0-1330W .49 (12.4) .7 (17.8) 27000 20000 300 546 (247)
2288 4/0-2109W .62 (17) .84 (21.3) 43000 30000 400 841 (381)

Grounding Ferrules
For lasting low resistance, compression Grounding Ferrules connect cable strands with a threaded stud that screws into a tapped boss on a clamp. Nut and lock washers increase contact pressure and secure the assembly. Use the aluminum ferrules on aluminum body clamps. The tin plated copper ferrules can be used on either bronze or aluminum body clamps. All Salisbury grounding ferrules are unshrouded and manufactured with a 5/8-11 UNC threaded stud.

Grounding Ferrules
Cat.
No.
ASTM
Grade
Size Insulating Die Codes Weight
lbs. (kg)
  T&B Alcoa Burndy Kearney  
Aluminum
2026 1 #2 50 08AH 243 9/16 .2 (.1)
2027 2 1/0 .2 (.1)
2620 3 2/0 60 09AH 245 11/16 .3 (.1)
4284 4 3/0 66 10AH 247 .840 .3 (.1)
2640 5 4/0 .3 (.1)
Copper
2022 1 #2 50 08AH 243 9/16 .5 (.2)
2023 2 1/0 .4 (.2)
2024 3 2/0 60 09AH 245 9/16 .4 (.2)
4277 4 3/0 66 10AH 247 .781 .6 (.3)
2025 5 4/0 .6 (.3)

Conductor & Cleaning Tools
4110 4337 4108
4113 4112 4111
Tubular Brushes are preferred when rubber gloving or working on de-energized conductors. The damage to rubber gloves is minimal because the steel bristles are internal. The 2.5” tubular brush is used in confined areas such as between two connectors or clamps. The “V” Type Wire Brush has an epoxy coated handle. Replacement brushes are available.
Cat.
No.
Description
in. (mm)
Weight
lbs. (kg)
4110 5" (127) Tubular .4 (.2)
4337 2.5" (63.5) Tubular .2 (.1)
4108 Universal Tubular 1.3 (.6)
4112 "V" Type handle w/brushes 1.2 (.6)
4113 "V" Type carton of 10 replacement brushes 3 (1.4)
4111 Universal "V" Line Cleaner 1 (.5)

Grounding Accessories
Pole Mounted Contact Bars are designed to act as a convenient common point for electrical connections and also as a hanger for jumper sets during installation and removal. Supplied with a 4’ chain and an adjustable wheel binder that will accommodate most common pole diameters. Catalog #20880 has one 5/8-11UNC tapped hole for the permanent connection of a ground lead. Strain Relief Sleeves reinforce cables at the termination points when used with the cable support system. This decreases strand damage to cables from age or mishandling which reduces current carrying capacity and service life. SALCOR® Strain Relief Sleeves are standard and accept all grounding cables #2 through 4/0. Sleeve assembly consists of two parts: the inner sleeve which is discarded if the cable diameter exceeds .72” and tapered outer sleeve, 6.5” long, which can be cut to match the diameters. Clear strain relief sleeves, for use with clear cables or for inspection purposes, are also available to fit ground clamps. Clear heat shrink is also available. The Salisbury 2103 Screw Type Temporary Ground Rod is used when an adequate system ground is not available. The design incorporates a copperweld rod with bronze fittings screwed and pinned on both ends. The terminal on the handle is designed to accept cables equipped with a 5/ 8-11 UNC threaded ferrule. As an alternative, a “C” clamp may also be attached directly to the ground rod shaft.

Grounding Accessories
Cat.
No.
Grade Description Weight
lbs. (kg)
Pole Mounted Contact Bars
9998 5 Contact Bar No Connection 4’ Chain w/ Adjustable Wheel Binder 9.1 (4.1)
20880 5 Contact Bar One Connection 4’ Chain w/ Adjustable Wheel Binder 9.1 (4.1)
Cable Strain Relief Sleeves
1788 Complete SALCOR Strain Relief Assembly .1 ( .04 )
1758 Inner SALCOR Sleeve Only .1 ( .04 )
0786 Tapered Outer SALCOR Sleeve Only .1 ( .04 )
2983 Clear Sleeve for #2 to 2.0 Grounding Cable .1 ( .04 )
2633 Clear Sleeve for 4.0 Grounding Cable .1 ( .04 )
20886 Clear Heat Shrink, 5”( 127mm ) for All Grounding Cables .1 ( .04 )
Screw Ground Rod
2103 75” ( 1.9m ) long 8 ( 3.6 )

Voltage Detectors — Audio / Visual
Voltage Detector 4445
Voltage Detectors are used to verify live or deenergized conductors. These testers may be used with rubber insulating gloves or hot sticks using the splined universal end fitting. Each tester has a 4.5 volt transistor amplifier with a audio/visual indicator. It is recommended that the tester be moved closer to conductor until warning is indicated, or it touches conductor, apparatus, or test point. Test the unit on a nearby energized conductor. To get verification of proper operation set tester on lowest setting. Each tester includes three “C” batteries.
The 4445 Voltage Detector Tester provides the most convenient and reliable means of verifying operation of voltage detectors. The tester is self contained and features instant push-button operation and requires a standard 9-volt battery. It’s portable and lightweight. To operate, push the button and move the tester toward the voltage detector being verified. An electric field activates the detector causing the audible and visual signals to operate.

Voltage Detectors — Audio / Visual
Test Procedures Troubleshooting
Test Procedures
To assure unit is in operable condition switch tester into “Test- 240V” position. The tester may now be tested in several different ways.
1. Place head as marked against live wire outlet or equivalent above 110V A.C.
2. Rub the head as marked on cloth or clothing to obtain static charge. Unit will only operate intermittently.
Trouble Shooting
Be sure the battery connection strap is bent to maintain pressure against batteries. Temperature range is -24°C to +70°C(-11°F to +158°F). Hold base and cap together when removing the handle. Do not assume conductors are dead or will remain de-energized. Always install proper grounding devices before working conductors.
Cat.
No.
Dimensions
in. (mm)
Settings Weight
lbs. (kg)
4444 11 x 3.5 ( 279.4 x 89 ) Off / Test-240V / Battery /URD:15kV/25kV/35kV
Overhead: 4.2kV / 15kV/25kV/35kV/46kV/69kV
15oz. (.43)
4244 11 x 3.5 ( 279.4 x 89 ) Off / 240V / 4.2kV / 15kV/25kV/35kV/69kV/115kV/230kV 15oz. (.43)
4344 11 x 3.5 ( 279.4 x 89 ) Off / 240V / 4.2kV /35kV/69kV/115kV/230kV/345kV/500kV 15oz. (.43)
Complete Kits
4356 1-4244 Tester 240V to 230kV, 1-4315 Case, 1-2500 Shotgun Adapter 2 ( .91 )
4367 1-4344 Tester 240V to 500kV, 1-4315 Case, 1-2500 Shotgun Adapter 2 ( .91 )
4469 1-4444 Tester 240V to 69kV, 1-4315 Case, 1-2500 Shotgun Adapter 2 ( .91 )
4445 Voltage Detector Tester 1 ( .45 )
4315 12 x 8 x 4.5 ( 5.45 x 3.6 x 2 ) Storage Case 1 (.45)
2500 Shotgun Adapter .4 ( .2 )

Voltage Detectors — Self Testing Audio / Visual
Salisbury’s Self-Testing Voltage Detectors allow testing to be continuous and automatic. An intermittent flash and beep confirms the detector is functioning properly.
Self-Testing Voltage Detectors are used to verify live or de-energized conductors. These testers may be used with rubber insulating gloves or hot sticks using the splined universal end fitting. Each tester has a 4.5 volt transistor amplifier with a audio/visual indicator. It is recommended that the tester be moved closer to conductor until warning is indicated, or it touches conductor, apparatus, or test point. Test the unit on a nearby energized conductor. To get verification of proper operation set tester on lowest setting. Each tester includes three “C” batteries.

Voltage Detectors — Self Testing Audio / Visual
Cat.
No.
Dimensions
in. (mm)
Settings Weight
lbs. (kg)
4544 11 x 3.5 (279.4 x 89) Off /240V/4.2kV/15kV/25kV/35kV/69kV/115kV/230kV 15oz. (.43)
4644 11 x 3.5 (279.4 x 89) Off /240V/4.2kV /35kV/69kV/115kV/230kV/345kV/500kV 15oz. (.43)
4744 11 x 3.5 (279.4 x 89) Off /Test-240V/Battery/URD:15kV/25kV/35kV
Overhead: 4.2kV / 15kV/25kV/35kV/46kV/69kV
15oz. (.43)
Complete Kits
4556 1-4544 Tester 240V to 230kV, 1-4315 Case, 1-2500 Shotgun Adapter 2 (.91)
4667 1-4644 Tester 240V to 500kV, 1-4315 Case, 1-2500 Shotgun Adapter 2 (.91)
4769 1-4744 Tester 240V to 69kV, 1-4315 Case, 1-2500 Shotgun Adapter 2 (.91)
4315 12 x 8 x 4.5 (5.45 x 3.6 x 2) Storage Case 1 (.45)
2500 Shotgun Adapter .4 (.2)

Hydraulic Cable Spike & Static Discharge Stick
24320 Spike Detail Static Discharge Stick
Hydraulic Cable Spikes are designed to verify that an underground power line-up to 1000 mcm-is de-energized before cutting, repairing, splicing or replacing.
The cable spike, a solid brass body with a stainless steel piercing tip, is fitted to hydraulic compression tools so that the cable can be accurately spiked from a safe distance. An anodized aluminum insert is included to position the cable precisely.
Improves Control, Accuracy and Safety. Saves Time, Remote Controlled

Adapter dapter fits the following tools:
Huskie EP610H
Burndy Y46
Brock 13-H.

The Static Discharge Stick is designed to safely remove the static charge after de-energizing. This grounding tool is pre-assembled and includes a brass alloy “U” hook, 4’ closed sell foam filled tubular fiberglass switch stick made in accordance with ASTM Standard F711. 6’ of copper grounding cable.

WARNING: ELECTRIC SHOCK HAZARD
This tool is not insulated. Use only certified, non-conductive hoses and proper personal protective equipment when using this unit. Failure to do so could result in severe injury or death.

Hydraulic Cable Spike & Static Discharge Stick
Cat.
No.
Cable Length
ft. (m)
Description Weight
lbs. (kg)
24320 6 (1.8) Spiking Tool & Grounding Assembly:
Cable Spiking Tool & Insert
4388A "C" Clamp
2139 4/0 Cu Cable
2025A 4/0 Cu Ferrules (Pair)
616 Bag
US Patent # 5447450
9.5 (4.3)
24321 8 (2.4) 11.2 (5.1)
24322 10 (3) 12.9 (5.86)
RPT1 Replacement Piercing Tip 1 oz. (28g)
Static Discharge Stick
20817 6 (1.8) Static Discharge Stick 4 ft. (1.2m) length 8 (3.6)

ASTM F855 Table — Grounding Cable Ferrule Ratings
Grade Cable
Size
Short Circuit Properties (A) — Symmetrical kA RMS 60 Hz Continuous
Current
Rating
RMS 60 Hz
Withstand Rating Ultimate Rating / Capacity (B, C)
15
Cycles
30
Cycles
6
Cycles
15
Cycles
30
Cycles
60
Cycles
1 2 14.5 10 30 19 13 9 200
2 1/0 21 15 48 30 21 15 250
3 2/0 27 20 60 38 27 19 300
4 3/0 36 25 76 48 34 24 350
5 4/0 43 30 96 60 43 30 400
6 250
MCM
54 39 113 71 50 35 450
7 350
MCM
74 54 155 100 71 50 550
A: Withstand and ultimate short circuit properties are based on performance with surges not exceeding 20% asymmetry factor
B: Ultimate rating represents a symmetrical current which the ferrule shall carry for the time specified.
C: Ultimate capacity represents a calculated symmetrical current which the cable is capable of conducting for the specified time. These currents are based upon the fusing (melting) current-time values for copper, derived from I.M. Onderdonk's equation.

WSP home page Products page Suppliers page  
Electrical
Safety
Salisbury
Index
Previous
Salisbury Page
Next