Justrite Safety Drum Vents and Fill Vents

Justrite Safety Drum Vents and Fill Vents

Manufacturer: Justrite

Product Code: 08101

Justrite Safety Drum Vents and Fill Vents

 

Prevent dangerous failure of drums storing flammables by using safety vents

  • Relieve pressure build-up due to heat.
  • Provide vacuum relief during sudden cooling or liquid drain-off.
  • Fits either 2-in (51-mm) or ¾-in (19-mm) bung opening on 30- or 55-gal (110- or 200-L) drums.

 

Provide emergency pressure venting in the event of a fire to avoid drum failure and catastrophic consequences. All safety drum vents automatically relieve pressure between 3 and 8 psi (30 to 55kPa) and include a flame arrester to absorb and safely dissipate heat. Valve within the vent is tested to allow 61 cubic inch (1-L) of water through a 3/8-in (9.5-mm) pipe nipple in less than 6 seconds for vacuum relief during drum dispensing operations. Vacuum relief permits smooth liquid flow and prevents possible drum collapse and leakage. Vacuum relief is automatic on vertically-installed vents and manual on horizontally-installed vents.

Justrite’s Aerovent™ fits a 2-in (51-mm) vertically-stored drum and has the same protection features of auto venting, auto vacuum relief, and a flame arrester as found in Justrite’s traditional safety vents—with the addition of a replaceable filter to control fugitive emissions. Brass body with an activated carbon filter adsorbs vapors and captures VOCs to keep them from escaping into the atmosphere during the exhale cycle. Use replacement filters when filter reaches full capacity or odors are present (approximately 90-120 days).

Safety fill vents and funnels fit the 2-in (51-mm) bung on a vertically-stored drum. The brass vent provides automatic pressure and vacuum relief, and includes a brass cap with safety chain tethered to the vent to prevent misplacement or loss. Remove cap during drum filling operations. Model no. 08211 includes a 9-in (229-mm) wide polyethylene funnel to facilitate solvent waste disposal and reduce spillage. Keep vent capped in closed position after filling operations to prevent flammable vapor from escaping. Six-inch (152-mm) flame arrester safely dissipates heat and prevents flashback from external ignition sources.

 

Safety Drum Vents

 

Description Vacuum
Relief
NPT/NPS Approv/Lstg Regulation Model No Ship Wt lb/kg
Brass vertical vent for petroleum-based applications Auto 2 in (DN50) FM 08101 2/1
Brass vertical vent assembly for 0.75 in (DN20) bung 0.75 in (DN20) 08102
Nonmetallic vertical vent, plated steel flame arrester,for petroleum based applications 2 in (DN50) 08005
Nonmetallic vertical vent, stainless steel flame arrester for chlorinated solvents 08006
Brass horizontal vent for petroleum-based applications Manual 08300
Stainless steel horizontal vent for corrosives and general solvents 08306
Cast-iron EL fitting for mounting vent nos. 08101 or 08006 in 2 in (DN50) bung opening 08011
Cast-iron EL fitting for mounting vent nos. 08101 or 08006 in 0.75 in (DN20) bung opening 08015
Aerovent™ brass drum vent for 2 in (DN50) bung with filter and one extra replacement filter Auto 2 in (DN50) FM 28206 12/6
Aerovent™ brass drum vent for 0.75 in (DN20) bung with filter and one extra replacement filter 0.75 in (DN20) 28207 10/5
Replacement filter (2-pack) for Aerovent™ drum vent 28198 3/2

 

Safety Fill Vents and Funnels

 

Description Vacuum Relief NPT/NPS Approv/Lstg Regulation Model No Ship Wt lb/kg
Fill vent with 9 in (229 mm) in polyethylene funnel, 6 in (152 mm) flame arrester Auto 2 in (DN50) FM 08211 4/2
Fill vent with 6 in (152 mm) flame arrester 08204
Polyethylene funnel only (no flame arrester) 08213 2/1

 

Approval and Compliance Key

FM Tested and approved by FM Approvals
UL/ULC Underwriters Laboratories listed in the U.S. and Canada
TÜV

TÜV Technical Inspection Association certified

N Complies with National Fire Protection Association (NFPA) Flammable and Combustible Liquids Code 30
O Complies with Occupational Safety and Health Administration (OSHA) Regulations
I Complies with the International Fire Code (IFC)
A Complies with NFPA 1 Fire Code - 2012 Edition
A9 Complies with NFPA 1 Fire Code - 2009 Edition
H Complies with NFPA 400 Hazardous Material Code
EN Complies with European standards EN 14470-1 and EN 14727
E Complies with Environmental Protection Agency (EPA) Regulations
S Supports EPA Spill Prevention, Control and Countermeasures Rule (SPCC)
V Validated by the EPA Environmental Technology Verification Program
Related Categories


Request a Quote Now

Request a Quote X

Your Name*
Please let us know your name.

Company Name
Invalid Input

Your Email*
Please let us know your email address.

Phone*
Invalid Input

Category*
Please enter valid Product/Category

Product Url
Enter valid Product Url

Comment
Please let us know your message.

Captcha*
Captcha   RefreshPlease enter the right CAPTCHA

Processing...