Lumidor Gas Detectors - New - Page 8

For more information, call Western Safety Products at 206-264-0808 or email sales@westernsafety.com.

Credit Card Images

 

Honeywell X5 Gas Detector
Honeywell X5 Gas Detector
• Small, lightweight design
• Simultaneously monitors up to five atmospheric hazards: VOCs, H2S, CO, CO2, O2, PH#, NH3, NO2, HCN, CI2, CIO2, O2, SO2, PH3 and NH3
• Compatible with MicroDock II, Honeywell’s automatic test/calibration docking station
• Available PID sensor enables sensitive broad spectrum monitoring of volatile organic compounds
• Water-resistant, concussion-proof enclosure
• User friendly—easy to operate and maintain with self-test, menu-driven interface, single-touch calibration
• Audible, vibrating and visual alarms, with four alarm levels: instantaneous Low and High Alarm for all gases, TWA (time-weighted average) and STEL (short-term exposure limit) for VOCs and toxics
• Continuous LCD shows simultaneous gas concentrations for five gases
• Simple, user selectable field options including PID / combustible correction factor, language selection, confidence beep, span level, set TWA/STEL calculation choice, set calibration due date, pass code protection, latching alarm, “SAFE” display function, stealth mode, and selectable ppm resolution for some gases

 

Specifications for X5 Gas Detector
DETECTOR: 1 , 2, 3, 4, or 5 -gas detector
Gas / Sensor Measuring Range Default Resolution High Resolution TWA *** STEL*** LOW *** HIGH***
O2 0-30.0% 0.50% N/A N/A N/A 19.5 23.5
H2S 0-500 ppm 1.0 ppm N/A 10 15 10 15
CO 0-999 ppm 1.0 ppm N/A 35 50 35 200
TwinTox (H2S) 0-500 ppm 1.0 ppm N/A 10 15 10 15
TwinTox (CO) 0-500 ppm 1.0 ppm N/A 35 50 35 200
PH3 0-5.0 ppm 1.0 ppm 0.1 ppm 0.3 1.0 0.3 1.0
SO2 0-150 ppm 1.0 ppm 0.1 ppm 2 5 2 5
NO2 0-99.9 ppm 1.0 ppm 0.1 ppm 2.0 5.0 2.0 5.0
HCN 0-30.0 ppm 1.0 ppm 0.1 ppm 4.7 10.0 4.7 10.0
Cl2 0-50.0 ppm 1.0 ppm 0.1 ppm 0.5 1.0 0.5 1.0
NH3 0-100 ppm 1.0 ppm 0.1 ppm 25 35 25 50
ClO2 0-1.00 ppm 0.1 ppm 0.01 ppm 0.1 0.3 0.1 0.3
O3 0-1.00 ppm 0.1 ppm 0.01 ppm 0.1 0.1 0.1 0.1
CO2 / IR 0-50,000 ppm 50 ppm N/A 5,000 30,000 5,000 30,000
0-5.0% v/v 0.01% N/A 0.5% 3.0% 0.5% 3.0%
VOC / PID 0-1000 ppm 1 ppm N/A 50 100 50 100
LEL 0-100% LEL 1% N/A N/A N/A 10% 20%
0-5.0% v/v 0.1% N/A N/A N/A 0.5% 1.0%
Use: Portable 5-gas monitor for the protection of personnel against gas hazards
Sensor Configuration*: One oxygen, one flammable, one toxic (can be TwinTox CO/H2S sensor or other); final position is either toxic, PID or IR sensor
Display: Custom LCD; Backlight: Low light (auto); alarm condition (auto); reactivation on demand
Weight: 13.1 oz / 370 g
Dimensions: 5.7 x 2.9 x 1.5 in/ 14.5 x 7.4 x 3.8 cm
Battery: Alkaline or optional Lithium Polymer rechargeable battery
Audible Alarm: 95 dB at 1 ft./30 cm at variable pulsed audible alarm
Vibrating Alarm: Pulses warning in gas alarm conditions, or for any status alarms
Visual Alarm: Two flashing alarm bars visible from all angles
Sensor Type: Electrochemical, catalytic bead and optional Infrared or PID
Calibration: Automatic (stand alone or with MicroDock II)
Data recording: All events and occurrences (calibration zero adjustment, calibration span adjustment, gas readings, TWA, STEL, alarm condition, failures detected by the microprocessor)
Intrinsic Safety: X5 and X5PID are II 1 G Ga Exia IIC T4 for ATEX and Ga Exia IIC T4 for IECEx; X5IR CO2 is II 2 G Ga Ex d ia
IIC T4 for ATEX and Ga Ex d ia IIC T4 for IECEx; Canada and the U.S. : Class I, Div.1 Gr. A,B,C, D T4. Certified
for combustible gas environments for Canada and the US: CAN/CSA C22.2 No.152 and ANSI ISA S12.13.1
Warranty: Two years including sensor except NH3 (one year)
* Contact Honeywell Analytics or a Honeywell Analytics distributor for allowable configurations
*** Note: alarm setpoints may vary by region

 

WSP home page Products page Suppliers page  
Gas Detectors Lumidor Index Previous Lumidor Page Next Lumidor Page