Spectrum SP Series Gas Detectors

Gas detectors are designed for monitoring the environment by one of two methods, diffusion or sample draw. In the case of diffusion, natural forces are relied upon to cause the ambient air to interact with the gas sensor. As an alternative, the air sample can be drawn to the sensor using either a hand-operated, squeeze-bulb aspirator or a motorized sample pump. Obviously, the motorized pump is much more convenient and easier to use, and it can provide a continuous air sample to the sensor at a constant flow rate.

Sample draw reduces gas response time compared to natural diffusion, and it facilitates testing of valves, pipe connections, etc. for leaks, and enables the monitoring of remote areas or enclosed vessels where non-ambient conditions may exist, such as, temperature extremes.

A properly designed sample draw system can improve the monitoring performance for most gases, particularly acid gases like CIg and HCI. It also reduces the response times for gases to be detected at sub-ppm con-centrations, such as, AsH3. And, most important, sample draw is required for the detection of some gases, most notably, HF and O3. It is for these reasons that the SPECTRUM SP Series was developed.
  • Built-in pump
  • Compact design
  • Backlit digital display
  • "Intelli-Cal" calibration procedure
  • Dual-level alarms
  • Password protected maintenance functions
  • Audio and visual alarms
  • Low battery alarm
Specifications
Size 5 x 4.75 x 2 inches (127 x 120 x 50 mm)
Weight 13 oz. (370 g)
Enclosure ABS plastic
Power Rechargeable 4.8 volt NiMH battery
Display 8 character, high contrast dot matrix LCD with backlight
Sensor Electrochemical
Alarm Points Two (high/low), audio & visual
Audible Alarm 75 dB at 10 cm, confidence chirp every 30 seconds
Visual Alarm Red LED
Temp Range 14 to 133ºF (-10 to +45ºC)

Ordering Information for Spectrum SP Gas Detector
Part No. Gas Detected Range LDL (1) Alarm (2) Alarm (3) Life (4) Cal/Test
04818-0100 Chlorine, Cl2 10.0 ppm 0.5 ppm 1 ppm 5 ppm 1-2 years 5
04818-0200 Hydrogen sulfide, H2S 200 ppm 5 ppm 10 ppm 25 ppm 2-3 years 5
04818-0400 Hydrogen chloride, HCl 20.0 ppm 1 ppm 5 ppm 10 ppm 1 year 5
04818-0500 Sulfur dioxide, SO2 20.0 ppm 1 ppm 5 ppm 10 ppm 2-3 years 5
04818-0700 Hydrogen fluoride, HF 10.0 ppm 1 ppm 3 ppm 6 ppm 1 year 6
04818-0800 Ozone, O3 0.99 ppm 0.05 ppm 0.10 ppm 0.20 ppm 1 year 7
04818-1200 Carbon monoxide, CO 1000 ppm 5 ppm 35 ppm 200 ppm 2-3 years 5
04818-1500 Hydrogen, H2 1000 ppm 30 ppm 200 ppm 750 ppm 2-3 years 5
04818-1700 Nitrogen dioxide, NO2 10.0 ppm 1.5 ppm 3 ppm 5 ppm 1-2 years 5
04818-1750 Nitric oxide NO 100 ppm 5 ppm 25 ppm 50 ppm 1-2 years 5
04818-2400 Ammonia, NH3 100 ppm 7 ppm 25 ppm 50 ppm 1 year 5
04818-4001 Arsine, AsH3 0.99 ppm 0.05 ppm 0.05 ppm 0.10 ppm 1 year 5
04818-4003 Silane, SiH4 30 ppm 4 ppm 5 ppm 10 ppm 1 year 5
(1) Lower Detectable Limit calculated from baseline noise level, thermal drift and interference data used to derive zero point deviation estimates
(2) Alarm adjustable, audio alarm acknowledgeable (can be silenced)
(3) Audio alarm reactivation, not acknowledgeable (cannot be silenced)
(4) Typical sensor life
(5) Gas cylinder and regulator available for calibration
(6) See HF permeation tube test kit
(7) See O3 generator test kit

Calibration / Test Equipment, Replacement Parts & Accessories for Spectrum SP
Description Part No. Description Part No.
HF Perm Tube Test Kit, with manual 04567-0702 Case, Gas Reg. and up to two 17 or 34 L cylinders 73083-000
O3 Generator Test Kit, 110 VAC with manual 04056-0800-4 Sampling Probe, 4' tubing w/10" rigid probe 03700-032
O3 Generator Test Kit, 220 VAC with manual 04056-0800-5 Battery for Spectrum SP, 4.8 V NiMH 67019-027
Gas Reg., flow demand, for 17L cyl. 03510-001 Charger for Spectrum SP, 110 VAC 67051-006
Gas Reg., flow demand, for 34L cyl. 03510-002 Charger for Spectrum SP, 220 VAC 67051-010
Connector Tube for Gas Reg./Sampling Probe 03700-033 Manual for Spectrum SP 80012-018

Calibration / Accessories
Ozone Generator
Test Kit Accessories not shown
34 & 17 liter calibration gas cylinders, regulators and connector tube HF Permeation Test Kit

MX-2100 Portable Gas Detector with 5-Gas Capability
  • Sensors available for more than 15 toxic gases, plus H2, O2 & LEL
  • Precalibrated for 32 combustible gases/vapors
  • 5-gas simultaneous detection
  • Up to 6 measurement ranges
  • Triple alarm system: audio, visual & vibratory
  • Invertible display for ease of reading
  • Zone 0 operation
  • Optional test and calibration station
  • Graphic display
  • Infrared port
  • Interchangeable, precalibrated smart sensors

Gases Detected by MX-2100
Gas Range Gas Range Gas Range
EXP* 100% LEL NO 300 H2 2000
CH4 100% LEL NO2 30.0 AsH3 1.00
O2 30% vol Cl2 10.0 SiH4 50
CO 1000 HCl 30.0 O3 1.00
H2S 100 HCN 30.0 HF 10.0
SO2 30.0 NH3 100 CO2 5.0% vol
* Calibrated with methan and programmed for 32 gases/vapors, including propane, butane, hexane, etc.

Specifications for MX-2100 Gas Detector
Function Multigas detector Power source Encapsulated NiMH battery pack (rechargeable, standard) or 3 AAA alkaline batteries
Configuration 3 channels: toxic gases, H2, O2
1 channel for explosive gases
Charger 12 to 30 volts DC
Sensors Smart, precalibrated, interchangeable without adjustment
Automatic sensor recognition
Charging Time 3 hours
State of charge displayed
Display Graphic LCD, text display of gas levels, Backlighting Operating Temp. 15ºF to 105ºF (-10ºC to +40ºC) continuous use
10ºF to 120ºF (-25ºC to +50ºC) intermittent use
Auto-Zero On demand, key function
Charger disconnect (option)
Ingress Protection IP 66
Gas Alarms Text message on display, for each channel
Flashing light signal, common to all channels
Audible signal, first alarm
Vibratory warning, first alarm
Weight 12 ounces (350 g)
Alarm Levels 2 instantaneous thresholds, per channel for LEL, O2, ppm H2, and toxid sensors Outputs (options) RS 232 infrared link
direct to printer for reviews
to PC , maintenance and supervision software including text output for Excel
Operating Check Self test at start up
Audible tone (factory set interval)
   
Warning Lights 360º visibility    
Audible Alarm 95 dB at 12 inches (30 cm)    
Approvals II 1G EEx ia IIC T4 (industry)
I M1 EEx ia IIC T4 (mining)
With IR/MOS sensor:
II 2G/I M2 EEx ia d IIC T4

INERIS 03 ATEX 0216
CE Mark
CSA pending

Options & Accessories for MX-2100 Gas Detector
Part No. Description
Instrument Package with Common Sensors
02610-000 MX-2100 Instrument with audio, visual and vibratory alarms, calibration shield/charger interface, power supply and CO, H2S, O2 and LEL sensors
Instrument Package without Sensors
02610-020 MX-2100 Instrument with audio, visual and vibratory alarms, calibration shield/charger interface and power supply, without sensors
See chart below for sensor specifications, part numbers and ordering information
Accessories
02612-005 Protective cover with harness
02612-006 Protective cover without harness
02612-010 Sampling pump (Also order p/n 03700-018 wand with probe or p/n 03700-031 hose, or both)
03700-018 Wand, 22 in. probe with 2 ft. hose
03700-031 Hose, 20 ft. with connector
02602-011 Hand aspirator with 12 ft. hose
02602-010 Hand aspirator with 27 in. probe and 3 ft. hose
73083-006 Transit case
02612-012 Software kit, COM2100, with IR/Serial cable
66014-002 Charger Adapter, 12 V DC

Sensor Part Numbers and Specifications For MX-2100
Part # Gas & Unit
of Measurement
Range LDL (5) Low
Alarm
High
Alarm
TWA
Alarm
STEL
Alarm
Life
(6)
Temp
ºC
02613-001-E (1) Combustible gas, % LEL (4) 100% LEL 1% LEL 10% LEL 50% LEL N/A N/A 24 -20 to +75
02613-0100-S (2) Chlorine, Cl2, ppm 10 ppm 0.5 ppm 0.5 ppm 1 ppm 0.5 ppm 1 ppm 24 -10 to +40
02613-0200-S (1) Hydrogen sulfide, H2S, ppm 100 ppm 5 ppm 10 ppm 15 ppm 10 ppm 15 ppm 24 -10 to +40
02613-0300-S Hydrogen cyanide, HCN, ppm 30 ppm 1 ppm 4.7 ppm 10 ppm 4.7 ppm 4.7 ppm 18 -10 to +40
02613-0400-S (2) Hydrogen chloride, HCl, ppm 30 ppm 1 ppm 5 ppm 10 ppm 5 ppm 5 ppm 18 -10 to +40
02613-0500-B Sulfur dioxide, SO2, ppm 30 ppm 1 ppm 2 ppm 5 ppm 2 ppm 5 ppm 24 -10 to +40
02613-0700-S (3) Hydrogen fluoride, HF, ppm 10 ppm 1 ppm 2 ppm 4 ppm 3 ppm 3 ppm 18 -10 to +40
02613-0800-S (3) Ozone, O3, ppm 1 ppm 0.05 ppm 0.1 ppm 0.2 ppm 0.05 ppm 0.2 ppm 18 -10 to +40
02613-1100-B (1) Oxygen, O2, % by vol 30% V 0.3%V 19.5%V 23.5%V N/A N/A 12 -10 to +40
02613-1200-S (1) Carbon monoxide, CO, ppm 1000 ppm 5 ppm 35 ppm 100 ppm 25 ppm 200 ppm 24 -10 to +40
02613-1350-B Carbon dioxide, % by vol 5.0%V 0.1%V 0.5%V 1%V 0.5%V 3%V 30 -10 to +40
02613-1500-S Hydrogen, H2, ppm 2000 ppm 30 ppm 200 ppm 2000 ppm N/A N/A 24 -10 to +40
02613-1700-S Nitrogen dioxide, NO2, ppm 30 ppm 1.5 ppm 2 ppm 4 ppm 3 ppm 5 ppm 24 -10 to +40
02613-1750-S Nitric oxide, NO, ppm 300 ppm 5 ppm 25 ppm 50 ppm 25 ppm 25 ppm 24 -10 to +40
02613-2200-B CO/H2S Combo sensor, ppm See Carbon monoxide and Hydrogen sulfide sensor data
02613-2400-S Ammonia, NH3, ppm 100 ppm 7 ppm 25 ppm 50 ppm 25 ppm 35 ppm 18 -10 to +40
02613-4001-S (2) Arsine, AsH3, ppm 1 ppm 0.05 ppm 0.05 ppm 0.1 ppm 0.05 ppm 0.1 ppm 18 -10 to +40
02613-4003-S Silane, SiH4, ppm 50 ppm 4 ppm 10 ppm 20 ppm 5 ppm 15 ppm 18 -10 to +40
(1) These are the replacement sensors for the standard instrument package, p/n 02610-0000
Warranty for the standard instrument package, including CO, H2S, LEL and O2 is 18 months from date of shipment
Warranty for all other sensors and accessories is 12 months from date of shipment
(2) For best performance, it is recommended that a sample pump be used for monitoring these gases
(3) A sample pump is required for monitoring these gases
(4) Calibrated with methane and programmed for 32 combustible gases/vapors including propane, butane, hexane, etc
(5) Lower Detectable Limit calculated from baseline noise level, thermal drift and interference data used to derive zero point deviation estimates
(6) Typical sensor life in months

Formaldemeter htV
The Formaldemeter htV offers a simple way to monitor levels of airborne formaldehyde in the environment. The instrument is easy to use with a simple four button keypad and features an easy-to-read four digit display. It employs a well-proven electrochemical formaldehyde sensor that will provide an immediate indication of formaldehyde levels. Unlike other formaldehyde monitoring devices, such as color stain tubes and badges, the Formaldemeter htV is capable of measuring many samples consecutively without the need for inconvenient ancillary equipment. Real-time results also mean that potential overexposures can be identified as they occur, without the delay and expense associated with laboratory analysis.
Also available: the Glutaraldemeter 3 for glutaraldehyde monitoring
  • Easy to use - minimal training required
  • Rapid response time
  • Small, hand-held instrument
  • Lightweight
  • Built-in sampling pump
  • Standard 9V alkaline battery operation
  • Temperature and humidity can also be displayed
  • Reliable electrochemical sensor
  • Simple in-field calibration
  • Optional base unit for continuous monitoring
Applications:
Formaldehyde is a common contaminant found in new construction, residential housing and commercial buildings following renovation. It is used in many products, industries and other types of activities, including:

Textile treatment
Medical labs
Laminated boards
Pharmaceuticals
Synthetic resins
Horticulture
Paints
Mortuaries
Paper products
Biological
Dye stuffs
Particle boards
Commercial buildings
Cosmetics
Residential construction
Hospitals

Specifications below:
Sensor: Electrochemical
Calibration: In-field formaldehyde calibration standard
Display: 4-digit LCD
Sampling Frequency: Typically once every 3 to 5 minutes depending on previous reading
Sample volume: Approx. 10 ml
Detection range: 0.05 - 10 ppm (optional high range: 80 ppm)
Precision: 10% at 2 ppm level
Response time: <10 seconds
Temperature: By key interrogation, displayed in degrees C
Humidity: By key interrogation, displayed in % rH
Power: 9 volt alkaline battery
Enclosure: ABS plastic
Weight: Instrument: 10 oz.
Complete Kit: 1.75 lbs.
Dimensions: Instrument: 6 x 3.25 x 1.25 inches
Carrying Case: 10.5 x 8.5 x 2 inches

Operation Details for Formaldemeter
Sampling:
  • Press the ON-OFF button
  • The display will show "---" followed by "0.00" (sensor ready)
  • Press the SAMPLE button
  • The display will show "run", followed by the sound of the pump sampling the air
  • The display indicates the measured concentration in approx. 10 seconds
  • Switch the instrument OFF (Instrument will automatically shut off after 5 minutes)

High levels, i.e., over 1 ppm, can take at least 5 minutes to "clear" from the sensor. If formaldehyde is detected, wait 3 - 5 minutes before turning instrument ON for next sample. To take another sample, repeat above steps.

Retrieval of stored data - instrument automatically stores the last ten readings

  • With the SAMPLE button depressed, press the ON-OFF button and then release
  • Instrument will display "HEAT" followed by the temperature in "C", alternating with humidity in % rH
  • With the instrument in this mode, press both CAL buttons simultaneously until the display shows "dAtA"
  • The display will now show "run0" followed by the result of the last sample
  • Scroll to the last ten results using the CAL buttons
Cross Sensitivity Chart
Compound ppm to = 1 ppm reading
Acetone No response
Acetaldehyde 8 - 12
Acetic Acid No response
Ammonia 71000
Butanol Note (2)
Carbon monoxide 100
Ethylene 160
Ethanol 12 - 20
Formaldehyde 1.0
Glutaraldehyde 7100 at 25ºC Note (3)
Methanol 50
Phenol 5, Note (1)
Propanol Note (2)
Resorcinol 5, Note (1)
Note (1) Completely removed with filter provided
Note (2) Interference above 60ºC and 20 ppm
Note (3) Monitor with Glutaraldemeter 3
Accessories and Replacement Parts:

Phenol Filters (supplied with instrument kit)
These filters can be used, when necessary, for the removal of phenol and resorcinol

Calibration Standard (supplied with instrument kit)
The calibration standard is a tube which produces a known concentration of formaldehyde vapor for testing and, if necessary, adjusting the accuracy of the monitor. The standard has a 100 sample capacity or a useful life of six months, whichever occurs sooner.

Options:

AMS-2 Base Unit
The base unit automates operation of the Formaldemeter htV for semi-continuous sampling. Monitoring of all three parameters (formaldehyde, temperature and humidity) is possible with the AMS-2, giving real time data and alarm (TWA/STEL) levels. A built-in printer provides a record of the results. All data is stored and can be downloaded to a PC via RS-232 and available download software.
AMS-2/htV Download Software
Data logged into the AMS-2 can be viewed on the LCD and outputted to the integral printer. If required, the data can be downloaded to most PC based spreadsheets using the AMS-2/htV download software

Ordering Information for Formaldemeter
Part Number Description
02700-100 Instrument kit with Formaldemeter htV, 10 phenol filters, thermometer, pen, calibration standard, instruction manual and case
02710-000 Instrument kit with Glutaraldemeter 3, 10 phenol filters, thermometer, pen, calibration standard, instruction manual and case
02700-251 Optional data logging station, Model AMS-2 Base Unit for htV
02700-256 Optional PC download software for AMS-2/htV
02700-001 Formaldehyde Calibration Standard, typical life 6 to 12 months
02710-001 Glutaraldehyde Calibration Standard, typical life 6 to 12 months
02700-002 Replacement Phenol Filters, pack of 10
02700-003 Replacement Formaldehyde Sensor, typical life 3 - 4 years