For more information, call Western Safety Products at 206-264-0808 or email sales@westernsafety.com.

![]() |
| ISA-40 Oxygen Monitor |
| Oxygen monitor |
| Specifications: Size / Wt.: 305 x 215 x 175 mm, 4 Kg Enclosure: NEMA-4X fiberglass Meter display: 16 to 26% by Volume Alarm point calibration: 19.5% by Volume Relays, Auxiliary: One latching SPDT (NO, NC) relay per channel; 2 amps steady, 5 amps surge Power: 110 / 220 VAC and / or 12 VDC Sensor type: Galvanic micro fuel cell Temperature range: 0 to 50 degrees C Sensor life: Average 12 to 15 months |
| ISA-44 Series multi channel systems ISA-44 series instruments feature MOS sensors for CO, H2S and ppm or LEL levels of organic solvents. Oxygen monitoring capability can also be included. ISA-44 systems are available for up to 10 channels |
| Examples of ISA-44 calibrations: CO: 35 and 100 ppm Calibrations available for HCN, ETO, Jet fuels, Ketones, Alcohols, Ethers, Halogenated hydrocarbons, Solvents, Esters, Butane, Hexane and others |
![]() |
![]() |
| Enguard 97D Stand alone |
Enguard MX-32 1 - 2 channels |
| Controller with integral or remote toxic sensor The economical Enguard 97D stand alone controller features either and integrated toxic gas sensor or an optional remote sensor and cable. Electrochemical sensors are available for O2 and a wide range of toxic gases
|
Controllers for remote sensors / Transmitters The Enguard series is an economical, versatile and reliable state of the art system designed to detect and monitor many different toxic and combustible gases. Single and multichannel systems are available.
Also available: |
![]() |
![]() |
| SDS-97D Series with digital display | EX-5100-MOS with MOS sensor (ppm solvents) |
![]() |
![]() |
| EN-Series without digital display | IR-6000 with infrared sensor (0 - 100% LEL) |
|
|
| Available for these gases:
AsH3, B2H6, Cl2, ClO2, CO, CO2, COCl2, ETO, HCl, HCN, HF, H2, H2S, NH3, NO, NO2, N2H4, O2, O3, PH3, SiH4, SO2, VCM, HCHO, F2, SiH2Cl2, HBr, BCl3, SF4, WF6, H2Se, Si2H6, Br2, I2, NF3, SF6 Note: sample pump required for some gases |
|
![]() |
![]() |
| ISA-RAL-M | ISA-200 |
| Specifications:
Alarm point: 10 ppm or 20 ppm CO |
Specifications:
CO and O2 Monitor |
![]() |
![]() |
| AFS-50 | AFS-50 on optional plate with ISA-RAL-M |
Features:
Specifications: Inlet pressure: Maximum 150 psi Can be supplied in the following configurations: In optional transit case: On optional wall mount plate: With optional CO / O2 Monitor |
|
| AFS-50 System and Options | |
| Description | Part No. |
| AFS-50 Air Filtration System. Supplied with mounting brackets | 03462-001 |
| Optional Plate, wall mounting. For ISA-RAL-M, ISA-200 Series CO or CO / O2 monitor and AFS-50 | 03262-002 |
| Optional Case. Holds AFS-50 and CO-RAL, 9 VDC, CO Monitor during transit and use | 03462-003 |
![]() |
|
19" Rack or Panel Mount gas detection system controller. This instrument control panel provides loop power and can monitor up to 16, 24-VDC, 4-20mA sensor/transmitters. The controller can be connected to any combination of 2-wire or 3-wire combustible gas, oxygen or toxic gas sensor/transmitters. A complete 16 channel system utilizes eight 2-channel circuit boards. Each channel, from 1 to 16 can be programmed to be either active (on) or inactive (off). A system with only one or two control cards can be purchased initially, and expanded later by adding plug-in channel cards.
|
|
| Specifications | |
| Channels | 1 - 16 independent channels |
| Mounting | 19" Rack or Panel mount. Fits 19" cabinet with 5-1/4" high panel space |
| Display | Fluorescent 2 lines, 16 characters, fixed or scrolling |
| Power | 110 VAC, 220 VAC or 24 VDC |
| Inputs | 4-20 mA, 24 VDC, 2-wire or 3-wire sensor/transmitters |
| Loop Power | 24 VDC provided |
| Outputs | 4-20 mA per channel, and system RS485 |
| Alarm Levels | 3 alarm levels per channel |
| Visual Indicators, per channel |
Active Channel: Green LED Gas Alarms: 3 Red LEDs Fault: Yellow LED |
| Audio Alarm | Horn activated by 1st gas alarm or fault |
| Relays | 2A, 250 VAC/30VDC, 2 per channel (1st and 2nd alarm) 1 system 3rd gas alarm 1 system fault relay |
| Languages | System programmable in English, French, German or Spanish |
| Programming Relays/Alarms |
Relays can be programmed to be latching or non-latching. Alarm relays 1 and 2 can be programmed for special fan control sequence. Relays 1 and 2 have a programmable time delay feature. System alarm relay 3 is programmable for time delay or average value activation |
| Sensor/Transmitters | Sensor/transmitters are available for a wide range of toxic and combustible gases. A partial list follows:
AsH3, B2H6, Cl2, ClO2, CO, CO2, COCl2, ETO, HCl, HCN, HF, H2, H2S, NH3, NO, NO2, N2H4, O2, O3, PH3, SiH4, SO2, VCM, VOCs, F2, SiH2Cl2, HBr, BCl3, SF4, WF6, H2Se, Si2H6, Br2, I2, NF3, SF6, TEOS, HCHO Sensor/transmitters are also available for organic solvents in ppm or % LEL, and combustible hydrocarbon gases in 0 - 100% LEL |
MX-42A |
MX-48 |
These instrument control modules can be used to power and monitor a variety of 24 VDC, 4-20 mA, sensor/transmitters. They can be connected to any combination of up to four (MX-42A) or eight (MX-48) oxygen, toxic or combustible gas sensor/transmitters.
|
|
| MX-42A | MX-48 | ||
| Channels | 1 - 4 Independent channels | Channels | 1 - 8 Independent channels |
| Enclosure | Shielded PVC enclosure | Enclosure | Painted steel enclosure |
| Rating | IP54 Ingress rating | Rating | IP65 Ingress rating |
| Display | LCD | Display | Fluorescent, 2 lines, 16 characters, fixed or scrolling |
| Weight | 11 lbs (4.9 kg) | Weight | 24 lbs (11 kg) |
| Size | 11-3/4"H x 13-1/2"Wx 4-1/4"D (300 x 340 x 107 mm) | Size | 13-1/2"H x 19-1/2"W x 3-1/2"D (340 x 500 x 89 mm) |
| Common Specifications | |||
| Inputs | 4-20 mA, 24 VDC, 2 or 3 wire sensor/transmitter | ||
| Loop Power | 24 VDC provided | ||
| Outputs | 4-20 mA per channel | ||
| Power | 110 VAC, 220 VAC or 24 VDC | ||
| Audio Alarm | Horn activated by 1st gas alarm, or fault | ||
| Relays | 2A, 250 VAC/30VDC, 2 per channel (1st & 2nd alarm) 1 system 3rd gas alarm 1 system fault relay |
||
| Programming, relays / alarms: Relays can be programmed to be latching or non-latching. Alarm relays 1 and 2 can be programmed for special fan control time sequence. Relays 1 and 2 have a programmable time delay feature. System alarm relay 3 is programmable for time delay or average value activation. |
|||
![]() |
Stand-alone controller with integral toxic gas sensor or optional remote sensor with cable. The Enguard 97D system is a self-contained single point gas monitor with an inegral sensor. As an option, the instrument can be supplied with a remote sensor on a six foot cable. This unique system includes a digital display, LED visual alarms, an audio alarm, and comes standard with an AC line cord. The unit is provided with three factory programmed alarm points.
|
| Controller Specifications | ||
| Size | 8.5"H x 7.6"W x 5"D (220 x 200 x 130 mm) | |
| Weight | 3 lbs. (1.36 kg) | |
| Enclosure | IP65, polycarbonate, wall mount | |
| Input Power | 85 - 265 VAC or 24 VDC | |
| Outputs | 4-20 mA; 5 VDC TTL outputs available for auxiliary alarm activation from three factory set points | |
| Relay | Single 2 amp 120 VAC relay, at one alarm level in conjunction with horn. User selectable from three factory set alarm levels | |
| Sensor Options | Enguard 97D comes standard with an integral sensor. As an option, the sensor can be supplied with a remote sensor housing and a six foot cable. Remote sensor is approx. 5" long x 1-3/4" diameter | |
| Monitors available for following gases: (table gives typical range and display resolution in ppm) | ||
| Gas | Range | Display |
| H2S | 0 - 100 | 1 |
| H2 | 0 - 2000 | 1 |
| SO2 | 0 - 30 | 0.1 |
| HCl | 0 - 30 | 0.1 |
| F2 | 0 - 1 | 0.01 |
| COCl2 | 0 - 1 | 0.01 |
| SiH4 | 0 - 30 | 0.1 |
| NO2 | 0 - 30 | 0.1 |
| AsH3 | 0 - 1 | 0.01 |
| ETO | 0 - 30 | 0.1 |
| CO | 0 - 500 | 1 |
| HCN | 0 - 30 | 0.1 |
| NO | 0 - 100 | 1 |
| HF | 0 - 10 | 0.1 |
| NH3 | 0 - 100 | 1 |
| PH3 | 0 - 1 | 0.01 |
| Cl2 | 0 - 10 | 0.1 |
| O3 | 0 - 1 | 0.01 |
| ClO2 | 0 - 1 | 0.01 |
| O2 | 0 - 30.0% | 0.1% |
| Calibration kits are available for all gases shown above | ||
![]() |
| A MOS sensor consists of a heated mixed metal oxide element that decreases in resistance in the presence of many gases and vapors. These sensors are broad range in their response characteristics. Different types of MOS sensors are available which can be optimized for a particular gas, but they are inherently non-specific. The MOS sensor can provide monitoring capability similar to that of the classic catalytic bead or hot wire sensor, but it can be calibrated for either %LEL or ppm detection levels of a wide range of hydrocarbons and organic solvents. The MOS sensor can also be used for detecting certain common toxic gases, including NH3, CO, H2S, etc. MOS sensors operate at a lower temperature than catalytic bead/hot-wire sensors, which makes them less prone to poisoning. The MOS sensor is therefore the sensor of choice in applications where, for example, lead, phosphates or sulfur containing compounds are present. Silicones, which are used in a wide range of oils, lubricants, adhesives and many other products can poison hot wire sensors and also influence the performance of MOS sensors under certain conditions. Applications for monitoring of hydrogen and hydrocarbon gases where silicones are present in the environment should be discussed with ENMET.
|
| Toxic | Combustible | ||
| Gas/Vapor | Range | Gas/Vapor | Range |
| Acetone | 2000 ppm | Acetone | 100% LEL |
| Ammonia | 300 ppm | Isopropyl Alcohol | 100% LEL |
| Methyl Alcohol | 400 ppm | Propane | 100% LEL |
| Methyl Chloride | 200 ppm | Vinyl Acetate | 100% LEL |
| Toluene | 400 ppm | Toluene | 100% LEL |
| MEK | 400 ppm | Gasoline | 100% LEL |
| Styrene | 100 ppm | Butane | 100% LEL |
| R-134A | 1000 ppm | Methane | 100% LEL |
| HFE-7100 | 100 ppm | Hydrogen | 100% LEL |
| Methylene Chloride | 200 ppm | Hexane | 100% LEL |
| Xylene | 400 ppm | Xylene | 100% LEL |
| In general, the EX-5150-MOS can be calibrated for combustible hydrocarbons, halogenated hydrocarbons, jet fuels, refrigerants, organic solvents, esters, ethers, alcohols, ketones, CO, H2S and other compounds and mixtures. | |||
| Voltage | 24 VDC, loop powered |
| Output | 4-20 mA |
| Installation | 3-wire, typically 16 to 18 AWG, depending upon distance |
| Connection | 1/2" NPT, conduit |
| Display | 8-character, single line, backlit LCD |
| Alarm Indicators | LEDs |
| Menu/Calibration | Magnet actuated switches |
| Sensor | MOS (metal oxide semiconductor) |
| Ordering Information | |
| Part Number | Description |
| 10014-008 | EX-5150-MOS, HV (calibration dependent) |
| 10014-009 | EX-5150-MOS, LV (calibration dependent) |
| 50030-001 | Replacement magnet |
| 80003-097 | Instruction manual |
| 73152-000 | Optional sealing fitting |
| 05006-001 | Optional relay PC board |
| For replacement sensors, check manual | |
| 03032-830 | Sensor HV, fluorocarbons/refrigerants |
| 03032-832 | Sensor HV, fluorocarbons/refrigerants |
| 03033-018 | Sensor HV, fluorocarbons/refrigerants |
| 03033-019 | Sensor HV, NH3 |
| 03033-109 | Sensor LV |
| 03033-812 | Sensor HV |
| 03033-813 | Sensor HV |
| Calibration Equipment | |
| 03700-001 | Calibration adapter, humidifier and regulator for 17 liter gas cylinders, for gases other than toluene and ammonia |
| 03700-005 | Calibration adapter, humidifier and regulator for 17 liter gas cylinders, toluene |
| 03700-009 | Calibration adapter, humidifier and regulator for 58 liter gas cylinders, ammonia (see part # 03230-300, 300/200 ppm) |
| 73083-000 | Case - holds calibration hardware and up to two 34 liter or two 17 liter gas cylinders |
| 73083-002 | Case - holds calibration hardware and up to four 17 liter gas cylinders or two 58 liter gas cylinders |
| Gas Samplers and Controllers | |
| Controllers: MX-32, MX-42A, MX-48 and MX-52 controllers are available, 1 to 16 channels | |
| Toxic gas sensor/transmitter: SDS-XXXX-97D series sensor/transmitters are available for monitoring oxygen and a wide range of toxic gases | |
| Combustible sensor/transmitter: the EX-5100 utilizes a pellistor/catalytic sensor for % LEL hydrocarbons | |
| Infrared sensor/transmitter: the IR-6000 is an infrared based sensor/transmitter for % LEL hydrocarbons | |
| WSP home | Products | Suppliers |